WATERLESS R-454B Tataiso ea ho Hlophisa Smart Logic Controller

R-454B Smart Logic Controller

Tlhahisoleseding ya Sehlahiswa

Litlhaloso:

  • Product Name: Smart Logic Controller (PLC FUNCTIONS &
    SEQUENCES) R-454B UNITS
  • Moetsi: Kakaretso ea Green Mfg.
  • Controlled Components: Thermostat/Zone Board, Air
    Handler/Furnace
  • Recommended Thermostat: Honeywell 8000 series thermostats

Litaelo tsa Tšebeliso ea Sehlahisoa

Mosebetsi o Nepahetseng oa Thepa:

Ensure the thermostat or zone board is connected to the
designated terminal strip, and the air handler or furnace is
connected to its respective terminal strip. Additional terminal
strips may be present based on the model type.

Heating and Cooling Functions:

  1. A Y call initiates heating or cooling. After 20 minutes, AUX
    heat will activate if needed. AUX heat remains on until the
    thermostat is fully satisfied.
  2. In cooling mode, the O signal triggers the reversing valve and
    e thibela tlhahiso ea mocheso oa aux.
  3. To save energy, the PLC cuts power to the crank case heater
    when the compressor runs.

WG2AH Forced Air with Hydronic Heating Function:

In addition to WG2A features, WG2AH units offer switching
priority from forced air to hydronic heating and Split Zone
tshebetso.

Switching Priority:

Use a jumper on the field wiring terminal strip between R and AW
to prioritize air heating over hydronic heating. Removing the
jumper makes hydronic heating the priority call.

Split Zone Feature:

Split Zone lets you heat one zone with hydronic heat and another
with forced air. Activate Split Zone by moving the jumper from R
and AW to R and SZ on the field wiring terminal block.

Lipotso tse atisang ho botsoa (FAQ)

Q: Can I use any thermostat with the Smart Logic
Molaoli?

A: Yes, the PLC program allows for the use of almost any
heat/cool thermostat, but Total Green Mfg. recommends using
Honeywell 8000 series thermostats for optimal performance.

"`

Smart Logic Controller
(PLC FUNCTIONS & SEQUENCES) R-454B UNITS
Likarolo le Litaelo
LIT-149 102824

Boithorollo
Ho kenya le ho fana ka litšebeletso tse nepahetseng tsa Total Green Mfg. Heat Pump ke ea bohlokoa bakeng sa ts'ebetso ea eona e tšepahalang. Lisebelisoa tsohle tsa Total Green Mfg. li tlameha ho kengoa le ho sebeletsoa ke rakonteraka ea nang le litsebo tsa HVAC. Boholo ba lisebelisoa, khetho le ho kenya ke boikarabello ba mokonteraka feela ea kenyang. Ho kenya thepa moahong o teng oa copper earth loop o sa lumellaneng le moralo oa hajoale oa Total Green Mfg. earth loop ha o lumelloe, o tla hlakola litiisetso tsohle tsa thepa, 'me ke boikarabello ba mokonteraka a le mong. Ho kenngoa ho tlameha ho etsoa ho latela litaelo tse boletsoeng bukeng ena. Ho hloleha ho fana ka ts'ebetso ke rakonteraka ea nang le litsebo tsa HVAC ka tsela e lumellanang le bukana ena ho tla hlakola le ho hlakola tšireletso e fokolang ea tiisetso ea sistimi. Total Green Mfg. e ke ke ea ikarabella bakeng sa sekoli leha e le sefe, ts'ebetso e sa khotsofatseng, ts'enyehelo kapa tahlehelo, ebang ke ka kotloloho kapa ka lebaka, mabapi le moralo, moetso, kaho, ts'ebeliso kapa ts'ebetso ea karolo efe kapa efe e boletsoeng.
All Total Green Mfg. forced air units will have separate terminal strips labeled “thermostat/zone board” and “air handler/furnace” for low voltage le PLC "e laoloa.
Bakeng sa ts'ebetso e nepahetseng ea lisebelisoa, thermostat kapa boto ea libaka e tlameha ho tlamelloa ho "thermostat/zone board terminal" strip. Sebapi sa moea kapa sebōpi se tlameha ho tlamelloa ho "setšoantšo sa moea / sebōpi" sa mohala. Ho tla boela ho be le li-terminal strips tse ling bakeng sa mesebetsi e fapaneng ho latela mofuta oa mohlala oo o ka sebetsang le ona. Lintlha tse fanoeng mona ke ho tlatselletsa bukana ea ho instola ka kotloloho yuniti ea hau.
IMPORTANT: For WGxA, WG2AH and WG2AD unit’s, if using a cased coil over a
furnace, do NOT program your thermostat for dual fuel mode or, use the furnace settings. Leave the thermostat set to electric aux. heat, otherwise, you may interfere with proper PLC function. Follow the dual fuel function option for the unit model you are installing. This information is detailed in your unit installation manual. You will also want to check the aux. heat cycle rate (CPH) setting in the thermostat and set this to 1 or, the lowest available value depending on your thermostat brand and model.

2

LIT-149 102824

Smart Logic Controller
WG1A E qobelloang ke Moea Feela Lenane la mesebetsi
1) The PLC checks that the LOW/HIGH pressure and discharge temperature switches are made. An open pressure switch input has a 60 second delay before setting a lockout and fault signal to “X”. This is to prevent nuisance calls, especially at the beginning of the cooling season when the Earth Loops are at their coldest. “X” is set with any hard lockout condition. Turning the low voltage ho yuniti ea kompressor e tima ebe o khutlela ho ts'ebetso ea ho koala hape ha feela mocheso oa mocheso o sa buleheng o sa buleha. Mocheso oa mocheso oa ho lahla o na le konopo ea ho tsosolosa ka letsoho. Mocheso o bulehileng oa mocheso o tla lula o hloka ho seta bocha ka letsoho hammoho le molumo o tlasetage matla potoloho. Li-switches tsa khatello lia iketsa.
2) A “Y” call starts heating or cooling. A 20-minute timer will bring on AUX heat should that time elapse without having satisfied the heating call. Once aux. heat is called, aux. heat will stay called until the thermostat fully satisfies.
3) Ho na le jumper e kentsoeng sebakeng sa "terminal terminal" e ngotsoeng "A" le "S". Ha jumper e kentsoe, yuniti e tla sebetsa ka sekhahla sa mocheso oa aux joalo ka tloaelo. Haeba jumper e tlosoa, PLC e kena ka har'a mefuta e 'meli ea mafura e emisang compressor ha ho na le mohala oa mocheso oa aux. Hang ha mohala oa mocheso o felile, sebali se phodileng sa metsotso e 5 se thibela compressor ho qala hape ka mohala oa "Y" ho fihlela nako e feta. Sena se lumella nako ea hore sebōpi se phole e le hore moea o chesang o se ke oa baka khatello e phahameng ea ho tsoa kapa ho koala ha konpresser e qala hape.
4) Ha thermostat e behiloe boemong ba ho pholile, lets'oao la "O" le matlafatsa valve e khutlisetsang morao 'me le notlela mocheso oa aux.
5) Boitekong ba ho fokotsa tšebeliso ea matla, PLC e tima motlakase ho heater ea crank case ha compressor e sebetsa.
6) This PLC program also allows the use of almost any heat/cool thermostat. Total Green Mfg. Strongly recommends using Honeywell 8000 series thermostats.
7) If either the compressor unit or, the air handler/cased coil sensor detects a refrigerant leak, the unit will go into lockout mode disabling the compressor and backup heat source. The blower on forced air units will be activated and, the “LA” (Leak Alert) light along with the “X” (Lock Out) will turn on along with the “LA” terminal being energized with 24 volts AC. This terminal can be used as a trigger, if required by your local building codes, to set off a remote alarm and/or trigger a mechanical room exhaust fan in the event of a refrigerant leak.

3

LIT-149 102824

Smart Logic Controller

WG2A E qobelloang ke Moea Feela Lenane la mesebetsi
1) PLC e hlahloba hore na khatello ea LOW / HGH le liphetoho tsa mocheso oa mocheso li etsoa. Mochine o bulehileng oa ho kenya khatello o na le tieho ea metsotsoana ea 60 pele o beha senotlolo le letšoao la phoso ho "X". Nakong ena ea bobeli ea 60, compressor e tla sebetsa feela ka 1st stage giving the system a chance to recover before setting a hard lock out. This is to prevent nuisance calls, especially at the beginning of the cooling season when the Earth Loops are at their coldest. “X” is set with any hard lockout condition. Turning the low voltage ho yuniti ea kompressor e tima ebe o khutlela ho ts'ebetso ea ho koala hape ha feela mocheso oa mocheso o sa buleheng o sa buleha. Mocheso oa mocheso oa ho lahla o na le konopo ea ho tsosolosa ka letsoho. Mocheso o bulehileng oa mocheso o tla lula o hloka ho seta bocha ka letsoho hammoho le molumo o tlasetage matla potoloho. Li-switches tsa khatello lia iketsa.
2) Mohala oa "Y1" o qala 1st stagho futhumatsa kapa ho pholisa ho tla tsoelapele ka metsotso e 20 ebe nako ea ho 2nd stagha nako eo e ka feta ntle le hore thermostat e letse "Y2". Haeba yuniti e le maemong a futhumatsang, hang 2nd stagE qala, sebali sa nako ea metsotso e 20 se tla tlisa mocheso oa AUX haeba nako eo e ka feta ntle le ho khotsofatsa mohala oa ho futhumatsa. Hang kaofela stagE 'nile ea bitsoa, ​​​​li tla lula li bitsoa ho fihlela thermostat e khotsofatsa ka botlalo.
3) Haeba mehala e fetang 3 e latellanang ea "Y1" e etsahala ntle le hore thermostat e letse 2nd s.tage ka hare ho metsotso e 20 kapa, pele ho metsotso e 20 2nd stage timer e felile, ka mohala oa bone oa "Y1", ho qalisoa potoloho ea tlhokomelo e tla tšoara le ho notlela sistimi ho 2nd s.tage bakeng sa metsotso ea 5 ho netefatsa hore oli e khutlela ho compressor. Haeba sistimi e arotsoe ka moea, "D" ea Zone Override e tla fana ka matla ho 24 volts. Joalo ka ha ho hlalositsoe bukeng ea ho kenya yuniti ea hau, lets'oao lena la 24-volt le ka sebelisoa hammoho le sebaka se fanoeng ke sebaka sa ho itšehla thajana ho letsetsa sebaka se seholo ka ho fetisisa le ho tšoara d.ampE bulehile hore sefuli se se bone khatello e phahameng ea static nakong ea metsotso e 5. Potoloho ea tlhokomelo e notlela mehala e meng ho fihlela e phethoa. Ka mor'a potoloho ea tlhokomelo, kapa haeba mohala oa "Y2" o etsoa pele potoloho ea tlhokomelo e etsahala, k'haontareng e khutlela ho zero. Sena se etsa hore sebaka sa rona se be bonolo kaha se lumella 2 stage futhumatsang le ho pholisa.
4) Ho na le jumper e kentsoeng sebakeng sa "terminal terminal" e ngotsoeng "A" le "S". Ha jumper e kentsoe, yuniti e tla sebetsa ka sekhahla sa mocheso oa aux joalo ka tloaelo. Haeba jumper e tlosoa, PLC e kena ka har'a mefuta e 'meli ea mafura e emisang compressor ha ho na le mohala oa mocheso oa aux. Hang ha mohala oa mocheso o felile, sebali se phodileng sa metsotso e 5 se thibela compressor ho qala hape ka mohala oa "Y" ho fihlela nako e feta. Sena se lumella nako ea hore sebōpi se phole e le hore moea o chesang o se ke oa baka khatello e phahameng ea ho tsoa kapa ho koala ha konpresser e qala hape.
5) Ha thermostat e behiloe boemong ba ho pholile, lets'oao la "O" le matlafatsa valve e khutlisetsang morao 'me le notlela mocheso oa aux.
6) Boitekong ba ho fokotsa tšebeliso ea matla, PLC e tima motlakase ho heater ea crank case ha compressor e sebetsa.

4

LIT-149 102824

Smart Logic Controller
7) This PLC program also allows the use of almost any heat/cool thermostat. Total Green Mfg. Strongly recommends using Honeywell 8000 series thermostats.
8) If either the compressor unit or, the air handler/cased coil sensor detects a refrigerant leak, the unit will go into lockout mode disabling the compressor and backup heat source. The blower on forced air units will be activated and, the “LA” (Leak Alert) light along with the “X” (Lock Out) will turn on along with the “LA” terminal being energized with 24 volts AC. This terminal can be used as a trigger, if required by your local building codes, to set off a remote alarm and/or trigger a mechanical room exhaust fan in the event of a refrigerant leak.
WG2AH Forced Air with Hydronic Heating Function
In addition to the function and features as described for WG2A units, The PLC program for the WG2AH units allows for switching priority call from forced air to hydronic heating as well as a feature called “Split Zone” that are installer optioned by choosing jumper settings as described below.
1) A jumper is used on the field wiring terminal strip between the “R” and “AW” terminals to prioritize air heating over hydronic heating. When this jumper is removed, hydronic heating becomes the priority call.
2) Split Zone is a feature which allows you the ability to heat one zone or floor with hydronic heat and another zone or floor with forced air. Split Zone is active by removing the priority call jumper across “R” and “AW” moving it across the “R” and “SZ” of the field wiring terminal block.
3) While in “Split Zone” mode, the compressor unit will provided forced air heating to the air zone. When the buffer storage tank calls for heat, the compressor unit will shift to heat water. Should a call for the air zone take place while the compressor unit is heating water, the call goes directly to the aux heat source to maintain the air zone. Once the tank temperature is satisfied, the system diverts back to normal air heating with the compressor unit.
1) When a hydronic heat call from the buffer tank takes place, the compressor turns off if it is running. 1 minute after that, the 3 way valve energizes and the SV1 valve de-energizes. 30 seconds after that stage, the water pumps starts to establish good water flow. 30 seconds after that stage, the compressor starts. Once the tank thermostat is satisfied, the compressor stops and the pump will continue to run for 30 seconds before turning off to gain any residual heat from the heat exchanger. 1 minute after the compressor stops, the 3-way valve de-energizes. 1 minute after that the compressor can restart for an air zone call. These timed cycles reduce system component wear by not having to shift under pressure or load.
4) The Hydronic heating function is disabled anytime the “O’ terminal is energized placing the unit in cooling mode.

5

LIT-149 102824

Smart Logic Controller
5) If either the compressor unit or, the air handler/cased coil sensor detects a refrigerant leak, the unit will go into lockout mode disabling the compressor and backup heat source. The blower on forced air units will be activated and, the “LA” (Leak Alert) light along with the “X” (Lock Out) will turn on along with the “LA” terminal being energized with 24 volts AC. This terminal can be used as a trigger, if required by your local building codes, to set off a remote alarm and/or trigger a mechanical room exhaust fan in the event of a refrigerant leak.
WG2AD Air Force e nang le Mosebetsi oa Ho futhumatsa Metsi ka Lehae
Ntle le ts'ebetso le likarolo tse hlalositsoeng bakeng sa li-unit tsa WG2A joalo ka ha ho hlalositsoe karolong ea pele ea tokomane ena, lenaneo la PLC bakeng sa li-unit tsa WG2AD le lumella ho fetola mohala o tlang pele ho tloha moeeng o qobelloang ho ea ho futhumatsa metsi a lapeng.
2) A jumper is used on the field wiring terminal strip between the “R” and “AW” terminals to prioritize air heating/cooling over domestic water heating. When this jumper is removed, domestic water heating becomes the priority call.
3) When a water heating call from the water tank takes place, the compressor turns off if it is running. 1 minute after that, the 3 way valve energizes and the SV1 valve de-energizes. 30 seconds after that stage, the water pumps starts to establish good water flow. 30 seconds after that stage, the compressor starts. Once the tank thermostat is satisfied, the compressor stops and the pump will continue to run for 30 seconds before turning off to gain any residual heat from the heat exchanger. 1 minute after the compressor stops, the 3-way valve de-energizes. 1 minute after that the compressor can restart for an air zone call. These timed cycles reduce system component wear by not having to shift under pressure or load.
4) An added functional PLC feature exclusive to the WG2AD model which allows water heating up 120 degrees, is the unit’s ability to maintain compressor stability by throttling the compressor load as needed to control discharge pressure.
5) If either the compressor unit or, the air handler/cased coil sensor detects a refrigerant leak, the unit will go into lockout mode disabling the compressor and backup heat source. The blower on forced air units will be activated and, the “LA” (Leak Alert) light along with the “X” (Lock Out) will turn on along with the “LA” terminal being energized with 24 volts AC. This terminal can be used as a trigger, if required by your local building codes, to set off a remote alarm and/or trigger a mechanical room exhaust fan in the event of a refrigerant leak.

6

LIT-149 102824

Smart Logic Controller
WG1H 100% Metsi a Heletsoeng le a Chesitsoeng ke Metsi a Chesang Feela Lenane la mesebetsi
1) PLC e hlahloba hore na khatello ea LOW / HIGH, HX Low le Discharge mocheso oa li-switches li etsoa. Kenyelletso e bulehileng ea switch ea polokeho e na le tieho ea metsotsoana e 60 pele e beha senotlolo le letšoao la phoso ho "X". Sena ke ho thibela mehala ea tšitiso, haholo-holo qalong ea sehla sa ho pholisa ha Earth Loops e bata haholo. "X" e setiloe ka boemo bofe kapa bofe bo thata ba ho notlela. Ho fetola molumo o tlasetage ho yuniti ea kompressor e tima ebe o khutlela ho ts'ebetso ea ho koala hape ha feela mocheso oa mocheso o sa buleheng o sa buleha. Mocheso oa mocheso oa ho lahla o na le konopo ea ho tsosolosa ka letsoho. Mocheso o bulehileng oa mocheso o tla lula o hloka ho seta bocha ka letsoho hammoho le molumo o tlasetage matla potoloho. Khatello le li-switches tsa mocheso oa HX Low lia ikemela.
2) Pitso ea "N" e qala pompo ea potoloho bakeng sa metsotsoana ea 30 pele ho compressor ho lumella ho phalla ka ho feletseng ka HX (mocheso oa mocheso) pele o qala mochine. Hang ha mohala o felile, pompo e tla eketsa metsotsoana e 30 ka mor'a hore compressor e eme ho hloekisa HX mocheso ofe kapa ofe o setseng. Sena se etsahala ho sa tsotelehe mohala oa metsi a futhumetseng kapa a batang.
3) If the compressor unit sensor detects a refrigerant leak, the unit will go into lockout mode disabling the compressor. The “LA” (Leak Alert) light along with the “X” (Lock Out) will turn on along with the “LA” terminal being energized with 24 volts AC. This terminal can be used as a trigger, if required by your local building codes, to set off a remote alarm and/or trigger a mechanical room exhaust fan in the event of a refrigerant leak.
Haeba u na le lipotso mabapi le efe kapa efe ea mesebetsi ena, ka kopo ikopanye le Total Green Mfg. ho 419-6782032 bakeng sa tšehetso ea tekheniki.