DAIKIN 1005-7 MicroTech Unit Remote Controller

Litlhaloso
- Lebitso la Sehlahiswa: Remote User Interface
- Compatibility: MicroTech Applied Rooftops, Air and Water-CooledChiller unit controllers
- Supported Models: Rebel Packaged Rooftop, Self-Contained Systems, and various other models
Selelekela
Lintlha tse akaretsang
- Bukana ena e hlalosa mokhoa oa ho kenya le ho sebelisa sehokelo sa mosebelisi se hole hore se sebelisoe le MicroTech Applied Rooftops hammoho le li-control tsa li-chiller tsa Air le Water-Cooled tse tsoang Daikin Applied.
- Bakeng sa tšehetso ea tekheniki holim'a marulelo kapa li-unit controller tse ikemetseng, ikopanye le Daikin Applied Air Technical Response Center ho 800-432-1342 (AAHTechSupport@daikinapplied.com).
- Bakeng sa tshehetso ya taolo ya yuniti ya chiller, ikopanye le Daikin Applied Chiller Technical Response Center ho 800-432-1342 (CHLTechSupport@daikinapplied.com).
- For technical support on PreciseLine unit controllers, contact the Daikin Applied Air Technical Response Center at 800-432-3928 (ATSTechSupport@daikinapplied.com)
Tlhahisoleseding ya Sehlahiswa
Sebopeho sa mosebelisi se hole se etselitsoe ho bonts'a, tlhophiso ea sistimi, ho seta, le taolo ea balaoli ba yuniti ea MicroTech:
| Mehlala ea MicroTech Unit Controller | |
| Rebel® Package Rooftop | Mehlala eohle |
| Rabele e Pakiloeng Rooftop | Mehlala eohle |
| Mekhoa e Ikemetseng | Mehlala ea SWT le SWP |
| Maverick® II Commercial Rooftop | Model MPS |
| Pathfinder® Air-Cooled Screw Chiller | Mefuta ea AWS le AWV |
| Trailblazer® Air-Cooled Scroll Compressor Chiller | Mefuta ea AGZ-D le AGZ-E |
| Magnitude® Water-Cooled Chiller | Model WME, B Vintage |
| Navigator® Metsi-Cooled Screw Chiller | Mohlala oa WWV/TWV |
| Trailblazer® Air-Cooled Chiller | Mohlala oa AMZ |
| PreciseLine® Air Handler | Mehlala eohle |
Ho phaella ho keypad / pontšo ea "unit mounted controller", mekhoa ea ho laola yuniti ea MicroTech e ka hlomelloa ka sebopeho se hole sa mosebelisi se sebetsanang le li-unit tse robeli ka sebopeho se le seng. Sehokelo sa mosebelisi se hole se fana ka phihlello ea tlhahlobo ea li-unit le litokiso tsa taolo tse ts'oanang le molaoli o kentsoeng yuniti.
Likaroloana
- Push-and-roll navigation wheel with an 8-line by 30- character display format
- Operating conditions, system alarms, control parameters and schedules are monitored
- RS-485 or KNX interface for local or remote installation
- Power from controller, no additional power supply necessary
- Supports panel mounting and wall mounting
Melaetsa ea Boitsebiso bo Kotsi
KOTSI
Kotsi e bontša boemo bo kotsi, bo tla fella ka lefu kapa kotsi e tebileng haeba e sa qojoe.
TLHOKOMELO
Tlhokomeliso e bontša maemo a kotsi, a ka bakang tšenyo ea thepa, kotsi ea botho, kapa lefu haeba a sa qojoe.
TLHOKOMELO
Tlhokomeliso e bonts'a maemo a kotsi, a ka bakang kotsi e nyane kapa tšenyo ea lisebelisoa haeba e sa qojoe.
TSEBISO
Tlhokomeliso e bontša mekhoa e sa amaneng le kotsi ea 'mele.
Litokomane tsa Litšupiso
| Nomoro | Khampani | Sehlooho | Mohloli |
| Tlhaloso: IOM 1202 | Daikin e sebelisoa | Pathfinder Chiller Model AWS Installation, Operation, and Maintenance Manual | www.DaikinApplied.com |
| Tlhaloso: IOM 1206 | Daikin e sebelisoa | Ho kenya Trailblazer Chiller Model AGZ, Buka ea Ts'ebetso le Tlhokomelo | |
| Tlhaloso: IOM 1242 | Daikin e sebelisoa | Pathfinder Model AWV Chiller Installation, Operation, and Maintenance Manual | |
| Tlhaloso: IOMM 1033 | Daikin e sebelisoa | Boholo Model WME, B vintage Magnetic Bearing Centrifugal Chiller Installation, Operation, and Maintenance Manual | |
| Tlhaloso: IOM 1264 | Daikin e sebelisoa | Moetso oa Navigator WWV/TWV Ho kenya Chiller e pholileng ka Metsi, Ts'ebetso, le Buka ea Tlhokomelo. | |
| Tlhaloso: IOM 1243 | Daikin e sebelisoa | Trailblazer Chiller Model AMZ | |
| OM 1382 | Daikin e sebelisoa | Rebel Commercial Packaged Rooftop Systems, Buka ea Tšebetso le Tlhokomelo | |
| OM 1373 | Daikin e sebelisoa | Rebel Applied Rooftop Systems, Buka ea Tšebetso le Tlhokomelo | |
| OM 1357 | Daikin e sebelisoa | PreciseLine Air Handler, Buka ea Tšebetso le Tlhokomelo |
Lintlha tsa Karolo
Kakaretso
Setšoantšo sa 1 se bonts'a lintlha tse mabapi le moralo oa li-hardware tsa basebelisi ba hole.
Kakaretso ea sebopeho sa 'mele e kenyelletsa:
- 5.7 × 3.8 × 1 in (144 × 96 × 26 mm) size
- 9.1 oz (256.7 g) weight, excluding packaging
- Ntlo ea polasetiki
Matla
- Supplied by the MicroTech unit controller for direct connection
- Separate 24V DAC power supply, optional for daisy chain connections, Max 85 mA
HLOKOMELA: Ikopanye le Daikin Applied Air Technical Response Center ho 800-432-1342 (AAHTechSupport@daikinapplied.com) or the Chiller Technical Response Center at 800-432-1342 (CHLTechSupport@daikinapplied.com) if a separate power supply is desired.
Pontšo
- LCD type FSTN
- Resolution dot-matrix 96 x 208
- Backlight blue or white, user selectable
Maemo a Tikoloho
- Operation EC 721-3-3
- Temperature -40…158°F (-40…+70°C)
- Restriction LCD -4…140°F (-20…+60°C)
- Restriction Process-Bus -13…158°F (-25….+70°C)
- Humidity < 90% RH (no condensation)
- Air pressure Min. 10.2 psi (700 hPa), corresponding to max. 9843 ft (3000 m) above sea level

Ho kenya
Kenyelletso pele
Ka kopo ela hloko tse latelang pele o kenya le ho kenya sehokelo sa mosebelisi se hole.
Litlhahlobo tsa Sebaka
Ho beoa ha sehokelo sa basebelisi ba hole hoa hlokahala ho netefatsa ts'ebetso e nepahetseng. Ha u khetha sebaka, qoba lintho tse latelang:
- Locations that are outside the operating temperature and humidity range (see Environmental Conditions.)
- Mounting on rooftop without a careful site evaluation and confirmation
- Walls that are subject to high vibration
- Areas with high humidity exterior walls and other walls that have a temperature differential between the two sides
- Areas that are close to heat sources such as sunlight, appliances, concealed pipes, chimneys, or other heat-generating equipment
Mount Surfaces
Bakeng sa ho kengoa ka holim'a metsi, beha sehokelo se hole sa mosebelisi sebakeng se bataletseng joalo ka sheet rock kapa plaster, control panel, kapa lebokose la mateano a motlakase.
- If mounting onto sheet rock or plaster, use anchors, if necessary
- For mounting in the unit controller panel, electrical junction box, or other metal enclosure, use the supplied magnets.
Likarolo
| Tlhaloso | Nomoro ea Karolo |
| MicroTech Remote User Interface | 1934080031,2 |
| Connectors (using CE+ CE- connection option) | 193410302 |
- Note that part number 193408001 is no longer available.
- For daisy-chaining unit controllers together, a 2-pin connector (PN 193410302), is required for each unit controller. The 2-pin connector is not required for direct-connecting unit controllers.
Ho fumana ofisi ea hau ea libaka, etela www.DaikinApplied.com kapa letsetsa 800-37PARTS (800-377-2787).

Ho hloella le ho hokela
Karolo e latelang e hlalosa mokhoa oa ho kenya sehokelo sa basebelisi ba hole le ho se hokahanya le balaoli ba yuniti e le 'ngoe kapa tse ngata tsa MicroTech.
TLHOKOMELO
Kotsi ea ho ntša motlakase. E ka baka tšenyo ea lisebelisoa.
Sesebelisoa sena se na le lisebelisoa tsa elektroniki tse ka senyehang ke ho tsoa ha electrostatic matsohong a hau. Pele o sebetsana le mojule oa puisano, o hloka ho ama ntho e theiloeng fatše, joalo ka sekoahelo sa tšepe, e le ho ntša matla a motlakase 'meleng oa hau.
TLHOKOMELO
Kotsi ea motlakase. E ka baka kotsi ea motho kapa tšenyo ea lisebelisoa.
Thepa ena e tlameha ho beoa fatše hantle. Ke basebetsi feela ba nang le tsebo ts'ebetsong ea lisebelisoa tse laoloang ba lokelang ho etsa likhokahano le tšebeletso ho molaoli oa lihlopha.
- Remove plastic cover (Figure 2).
- Mount the remote user interface. The remote user interface can be either panel mounted or wall mounted as shown in Figure 3. See Figure 4 and Figure 5 for terminal connections for each of the mounting locations.
Ho Wiring Remote User Interface
Ho hokahanya sebopeho sa mosebelisi se hole ho molaoli oa yuniti ea MicroTech ho ka etsoa ka mekhoa e 'meli e fapaneng:
- Daisy-chain connection to as many as eight units.
- Direct connection to a single unit controller.
Litaelo tsa ho hokahanya le lithapo boemong bo bong le bo bong li hlalositsoe karolong e latelang. Sheba Lethathamo la 1 bakeng sa boholo ba terata le meeli ea sebaka.
HLOKOMELA: Power is supplied by the MicroTech unit controller. If a separate 24V power supply is desired, please contact either the Daikin Applied Air Technical Response Center at 800-432-1342 (AAHTechSupport@daikinapplied.com) or the Chiller Technical Response Center at 800-432-1342 (CHLTechSupport@daikinapplied.com).
Khokahano ea Daisy-Chain
Theha khokahano ea 'mele ho tloha ho sehokelo sa mosebelisi se hole ho ea ho molaoli oa yuniti ea MicroTech.
- Connect a twisted pair wire to the CE + and CE – pins of each unit controller and remote user interface (see Figure 4 and Figure 5).
- Daisy-chain up to eight MicroTech unit controllers to a single remote user interface. See Figure 5 for wiring details. Note the wire size and distance limitations provided in Table 1.
- Cycle power to each MicroTech unit controller once the wiring of the remote user interface is complete.
HLOKOMELA: Downloading and communication using the daisy- chain connection may be slower than for the RJ45 (Ethernet) direct connection.
Tafole 1: Wiring Specifications
| Khokahano ea libese | CE+, CE-, not interchangeable |
| Theminale | 2-screw connector |
| Max. bolelele | 1000 ft (305 m) |
| Mofuta oa thapo | |
| Wiring distance up to 500 ft | Twisted pair, shielded cable 16 AWG |
| Wiring distance between 500 – 1000 ft | Twisted pair, shielded cable 14 AWG |
| Sebaka sa marang-rang se fetang 1000 ft | Not currently supported. Contact the appropriate Daikin Applied Technical Response Center for assistance. |

Khokahano e Otlolohileng
Sehokelo sa mosebelisi se hole se ka kengoa ka mohala ka kotloloho ho molaoli a le mong oa yuniti ea MicroTech holim'a khokahano e tloaelehileng ea RJ45 (Ethernet).
Tsamaiso
- Locate the connector location as shown in Figure 6
- Follow Figure 6 for connection details. Note the distance limitations provided.
- Cycle power to the unit(s) once the wiring of the remote user interface is complete.

HLOKOMELA: Power is supplied by the unit controller. If a separate 24V power supply is desired, please contact either the Daikin Applied Air Technical Response Center at 800-432-1342 (AAHTechSupport@daikinapplied.com) or the Chiller Technical Response Center at 800-432-1342 (CHLTechSupport@daikinapplied.com).
Ho sebelisa Remote User Interface
Likarolo tsa Hardware
Konopo / ponts'o ea mosebelisi e hole e na le ponts'o ea litlhaku tse 8 ho isa ho tse 30, lebili la "push and roll", le likonopo tse tharo: Alamo, Menu, le Morao (Setšoantšo sa 7).
- Turn the navigation wheel clockwise (right) or counterclockwise (left) to navigate between lines on a screen and also to increase and decrease changeable values when editing. Press down on the wheel to use it as an Enter button.
- Press the Back button to display the previous page.
- Press the Home button to return to the main screen from the current page.
- Press the Alarm button to view ho menu ea Alarm Lists.
Keypad/Dikarolo tsa Pontsho
The first line on each page includes the page title and the line number to which the cursor is currently “pointing.” The line numbers are X/Y to indicate line number X of a total of Y lines for that page. The left most position of the title line includes an “up” arrow to indicate there are pages “above” the currently displayed items, a “down” arrow to indicate there are pages “below” the currently displayed items or an “up/down” arrow to indicate there are pages “above and below” the currently displayed page. Each line on a page can contain status-only information or include changeable data fields. When a line contains status-only information and the cursor is on that line, all but the value field of that line is highlighted meaning the text is white with a black box around it. When the line contains a changeable value and the cursor is at that line, the entire line is highlighted.
Mohala o mong le o mong leqepheng o ka boela oa hlalosoa e le mola oa "tlola", ho bolelang hore ho sututsa lebili la ho tsamaea ho tla baka "tlola" leqepheng le lecha. Motsu o bonts'itsoe ka ho le letona la moeli ho bontša hore ke "tlola" 'me mola oohle o totobatsoa ha sesupa se le moleng oo.
HLOKOMELA: Only menus and items that are applicable to the specific unit configuration are displayed.
Setšoantšo 7: Remote User Interface Main Features

Dialamo
Lenane la Lintlha tsa Alamo le kenyelletsa alamo e sebetsang le tlhaiso-leseling ea tlaleho ea alamo. Sheba setšoantšo sa 8 bakeng sa example of an active alarm. Also refer to the appropriate MicroTech unit controller Operation Manual (www.DaikinApplied.com) for available alarm options.
Setšoantšo 8: Alarm Details Menu

Li-password
Mesebetsi ea menu ea "unit controller" e na le maemo a fapaneng a phihlello. Bokhoni ba ho view le/kapa ho fetola litlhophiso ho ipapisitse le boemo ba phihlello ba mosebelisi le password e kentsoeng. Ho na le maemo a mane a phihlello ea password:
- No password.
- Level 2. The highest level of access. Without entering a password, the user has access only to basic status menu items. Entering the Level 2 password (6363) allows similar access as Level 4 with the addition of the Unit Configuration Menu.
- Level 4. Entering the Level 4 password (2526) allows similar access as Level 6 with the addition of the Commission Unit Menu, Manual Control, and Service Menu groups.
- Level 6. Entering the Level 6 password (5321) allows access to the Alarm Lists Menu, Quick Menu, and the View/Beha sehlopha sa Menu ea Yuniti.
HLOKOMELA: Alarms can be acknowledged without entering a password.
Ho kena Leqepheng la Phasewete
Leqephe le ka sehloohong la password le bonts'oa ha "remote user interface" (HMI) e qala ho fihlella.
- Tobetsa konopo ea Lehae.
- Press the Back button multiple times, or if the keypad/display has been idle longer than the Password Timeout (default 10 minutes).
Leqephe le ka sehloohong la password le fana ka phihlello ea ho kenya phasewete, ho fihlella Quick Menu, view Unit State ea hajoale, fihlella manane a alamo kapa view tlhahisoleseding mabapi le yuniti (setšoantšo sa 9).

The MicroTech unit controller Operation Manual
(www.DaikinApplied.com) provides additional information about passwords, including how to use the Navigation and Edit Mode settings to access and modify passwords.
Tlhophiso
The following section describes how to set up the HMI so that it can be used to display, configure, or change unit parameters. Refer to the applicable MicroTech unit controller Operation Manual for a detailed description of chiller or rooftop sequence of operation and keypad menu structure when configuring the unit via the remote user interface (www.DaikinApplied.com).
HLOKOMELA: To toggle between units, press the Back button for five seconds to return to the main screen.
Iketsetse Likhetho tsa Mosebelisi
- Turn power on to the unit controller(s). Power to the remote user interface is provided automatically from the MicroTech unit controller(s) through the RJ45 (Ethernet) direct connection.
- The main screen with HMI Settings and Controller List appears (Figure 10).
Sebelisa skrine ea Litlhophiso tsa HMI ho fetola likhetho tsa 'mala oa lebone la morao, nako ea ho tima lebone la morao, phapang le khanya.
HLOKOMELA: The main screen can be accessed at any time by pressing the Home button for five seconds. - Press the navigation wheel to select the HMI Settings menu, if desired.

Amahanya le MicroTech Unit Controller
- Press the navigation wheel to select the Controller List screen (Figure 11).
- The Controller List automatically updates each time the remote user interface is powered up so that information is synchronized from the main unit controller.
- The Controller List screen displays the unit controller(s) connected to the remote user interface. This screen allows the user to select between units, if more than one unit is connected to the remote user interface
ELA HLOKO: Ho hlaha yuniti e le 'ngoe skrineng e le monyetla oa khetho haeba ho hoketsoe taolo ea yuniti e le 'ngoe feela ho sehokelo sa mosebelisi se hole.
- Turn the navigation wheel clockwise and then press down to select the desired unit.
- The Information screen appears as the remote user interface performs a download sequence to import the necessary information from the main unit controller. A status bar appears on the Downloading the Objects screen to indicate that the download is in process (Figure 12).
HLOKOMELA: Refer to the Troubleshooting section if the remote user interface appears to “freeze” during the initial downloading sequence.
- The Information screen appears as the remote user interface performs a download sequence to import the necessary information from the main unit controller. A status bar appears on the Downloading the Objects screen to indicate that the download is in process (Figure 12).
- Once the first unit has been downloaded, select the next unit controller, if applicable. The download process is required for each unit controller connected to the remote user interface.
- Press the Home button for five seconds to return to the main screen.
HLOKOMELA: The Downloading the Objects sequence generally takes a minute or less when direct-connecting to a single unit. However, the downloading sequence takes longer when using the daisy-chain connection.
Ha tatelano ea ho jarolla e phethiloe, skrine e kholo ea molaoli oa yuniti e hlaha ho sehokelo sa mosebelisi se hole. Mothating ona, sebopeho sa mosebelisi se hole le taolo ea yuniti li hokahantsoe. - Access and adjust the same parameters that are available via the unit controller keypad/display. Refer to the applicable MicroTech unit controller Operation Manual for the keypad menu structure and detailed description the unit controller sequence of operation (www.DaikinApplied.com).
Mokhoa oa ho ntlafatsa firmware
Latela mehato ena ho nchafatsa "remote user interface" (HMI) firmware (.bin) file.
HLOKOMELA: The upgrade procedure requires the use of an SD memory card no larger than 8GB with a FAT32 file sebopeho sa sistimi.
TLHOKOMELISO: Ha ho khonehe ho nchafatsa li-unit tse nang le firmware ea v1.07. Ikopanye le Daikin Applied Air Technical Response Center ho 800-432-1342 (AAHTechSupport@daikinapplied.com) or the Chiller Technical Response Center at 800-432-1342 (CHLTechSupport@daikinapplied.com) bakeng sa thuso.
Ho ntlafatsa ho tloha VVS10 ho ea ho mofuta o mocha
- Kenya firmware file, POL12289.bin, ho SD-Card bukeng ea metso e se nang tse ling files.
- Insert the SD Card into the MicroTech unit controller. The unit controller must be powered-up and running.
- Connect the HMI DM to the unit controller.
- Press the back button of the HMI DM until the “HMI Setting and Local Connection” page appears.
- Choose the HMI Setting. Scroll to the end of this page and the “Firmware Update” option appears.
- Push and roll to YES. Push the knob of the HMI DM again.
- The “Now Firmware Updating” message appears on the user HMI display.
Se ke oa tlosa matla ho sesebelisoa sa motlakase. - After successful upgrade of the firmware, the HMI DM goes back to the normal HMI page.
- Follow steps 1-4 to upgrade firmware for each HMI on a daisy-chain network. Please be aware that each remote user interface must use the same firmware version.
Ho batle phoso
Karolo ena e na le lintlha tse thusang, lipotso tse botsoang khafetsa, le malebela a mang a amanang le sehokelo sa basebelisi ba hole.
Tafole 2: Troubleshooting Guide
| Bothata | Tharollo |
| During the initial download sequence, the keypad/display appears to freeze up and a “Loading…. Lost Connection” message appears. | The remote user interface is stuck in the downloading sequence due to incompatibility with v1.07 application software. The remote user interface must be updated to v10.22 or newer application software. Contact Daikin Applied Air Technical Response at 800-432-1342 bakeng sa litaelo tse ling. |
| The remote user interface has been connected to the MicroTech unit controller but the display remains blank after power-up. | Netefatsa hore yuniti controller e na le matla. Sheba lithapo ho tloha ho molaoli oa yuniti ho ea ho sehokelo sa mosebelisi se hole. Hlokomela hore lintho tse kenang le tse hlahisoang li na le polarity-sensitive. |
| Sehokelo sa mosebelisi se hole se na le tahlehelo ea puisano. | Sebaka sena se ka ba le "matla a litšila" kapa lerata la motlakase le bakang tahlehelo ea puisano. Sheba ka tlase bakeng sa litaelo tse ling. |
- Access the Power Bus menu on the MicroTech unit controller by the following keypad menu path: service menu/HMI setup/PBusPwrSply=ON (default). See Figure 13.
- Set the default Power Bus supply.
- For the first and last units on the daisy-chain trunk, leave the Power Bus supply at the default of ON.
- For all other units within the daisy chain trunk, set the Power Bus supply to the OFF position.

Malebela a Thusang
Hangata litsebi tsa lits'ebeletso li fumana ho le bonolo ho ba le likonopo/lits'oants'o tse peli tse hokahantsoeng le taolo ea yuniti e le 'ngoe. Ho sebelisa setupo se arohaneng skrineng ho etsa hore ho khonehe ho view lintho tse ngata tsa menu ka nako e le 'ngoe nakong ea ho qala le bakeng sa merero ea ho hlahloba.
Hokela feela sehokelo sa pele se hole sa mosebelisi se nang le khokahanyo e tobileng ea RJ45, ebe u sebelisa thapo e sothehileng ea terata e 'meli ho hokela konopo ea bobeli/pontšo.
Nalane ea Phetoho
| Khatiso | Letsatsi | Liphetoho |
| Setšoantšo sa IM1005 | Pherekhong 2010 | Tokollo ea pele |
| Setšoantšo sa IM 1005-1 | Loetse 2010 | Added Daikin Trailblazer® chiller model AGZ-D |
| Setšoantšo sa IM 1005-2 | Hlakubele 2012 | Added Rebel® packaged rooftop model DPS. Updated Figure 3 with labels and connector cables. |
| Setšoantšo sa IM 1005-3 | La 2016 Pulungoana XNUMX | Added models AWV Pathfinder® chiller and AGZ-E Trailblazer® chiller, added RJ45 direct connection option, corrected bus wiring distance limitations, Troubleshooting section, Daikin branding and formatting updates |
| Setšoantšo sa IM 1005-4 | Pherekhong 2018 | E kentse mefuta ea WME & WWV chiller. |
| Setšoantšo sa IM 1005-5 | Phato 2019 | Updated connections |
| Setšoantšo sa IM 1005-6 | Phuptjane 2023 | Branding le liapdeite tse ling tsa ho fometa. |
| Setšoantšo sa IM 1005-7 | Phupu 2025 | Updated contact information, added Daikin Trailblazer® chiller model AMZ, and removed model lists from front cover. |
Koetliso le Nts'etsopele ea Daikin e sebelisitsoeng
Kaha joale u se u entse letsete ho thepa ea kajeno, e sebetsang ea Daikin Applied, tlhokomelo ea eona e lokela ho ba ntho ea bohlokoa ka ho fetisisa. Bakeng sa tlhaiso-leseling ea koetliso mabapi le lihlahisoa tsohle tsa Daikin Applied HVAC, ka kopo re etele ho www.DaikinApplied.com ebe o tobetsa Thupelo, kapa letsetsa 540-248-9646 le ho kopa Lefapha la Koetliso.
Tiisetso
Thepa eohle ea Daikin Applied e rekisoa ho latela lipehelo tsa eona tse tloaelehileng le maemo a thekiso, ho kenyeletsoa Tiisetso e Lekanyelitsoeng ea Sehlahisoa. Ikopanye le Moemeli oa hau oa lehae oa Daikin bakeng sa lintlha tsa tiisetso. Ho fumana moemeli oa hau oa lehae oa Daikin Applied, e ea ho www.DaikinApplied.com.
Litšebeletso tsa Aftermarket
Ho fumana ofisi ea hau ea libaka, etela www.DaikinApplied.com kapa letsetsa 800-37PARTS (800-377-2787). Ho fumana ofisi ea hau ea litšebeletso sebakeng sa heno, etela www.DaikinApplied.com kapa letsa 800-432-1342.
Tokomane ena e na le lintlha tsa morao-rao tsa sehlahisoa ho tloha khatisong ena. Ho fumana lintlha tsa morao-rao tsa sehlahisoa, ka kopo, etela ho www.DaikinApplied.com.
Lihlahisoa tse entsoeng setsing se netefalitsoeng sa ISO.
Lipotso Tse Botsoang Hangata
How many units can be controlled per remote interface?
The remote user interface can handle up to eight units per interface.