

XTH2 & XTD2 Temperature Transmitters – Fixed Range
XTH2 Series
XTD2 Series
XTH2 & XTD2 product insert
AutomationDirect.com
Ho kenya
- XTH2 Transmitter comes with installation screw kit
- Ambient Temperature: -40 to 185°F (-40 to 85°C)
- Sebaka sa ho kenya:
Field housing; connection head Form B according to DIN 43729 - Installation angle: No limit
Hlokomela: Max. mounting screw torque: 3/4 lb·ft (1 N·m)

Litekanyo
mm [li-inch]

Head transmitter type with screw terminals.
A – Spring travel L ≥ 5 mm
B – Mounting elements for attachable measured value display
Screw terminals – 24.1 mm (0.95 in)
Installation of DIN Rail transmitter

Mount the device vertically and ensure it is correctly oriented.
- Slide the device top DIN rail groove onto the top of the DIN rail.
- Rotate the device into the bottom of the DIN rail, until you can hear the DIN rail clip click into place on the DIN rail edge.
- Pull gently on the device to check secure mounting on the DIN rail.
mm [li-inch]

DIN Rail transmitter with screw terminals.
- Operating Ambient Temperature Range: -40 to 185°F (-40 to 85°C)
- Installation angle: No limit
Wiring Head Type

Litaelo tsa polokeho:
- To comply with UL61010-1 unit must be supplied by class 2 power supply.
- Disconnect power before making connections.

Tshireletso
Please take note: When installing the head style transmitter remotely from the sensor in a field housing, the shield on the 4-20 mA signal output must have the same potential as the shield at the sensor connections. When using grounded thermocouples, shielding of the output 4-20 mA cable is recommended. In facilities with strong electromagnetic fields, shielding of all cables with a low Ohm connection to the transmitter housing is recommended.
Due to the danger of lightning strikes it is recommended that shielded cable be used in outdoor installations.
Wiring DIN Type

Litaelo tsa polokeho:
- To comply with UL61010-1 unit must be supplied by class 2 power supply.
- Disconnect power before making connections.
Loaro Impedans

Tshireletso
The shield on the 4-20 mA signal output cable must have the same potential as the shield at the sensor connections. When using grounded thermocouples, shielding of the output 4-20 mA cable is recommended. In facilities with strong electromagnetic fields, shielding of all cables with a low Ohm connection to the transmitter housing is recommended.
Due to the danger of lightning strikes it is recommended that shielded cable be used in outdoor installations.
Ke kopa o etele www.automationdirect.com for specifications and additional information.
Litokomane / Lisebelisoa
![]() |
AutomationDirect XTD2-0100F-J Temperature Transmitter [pdf] Tlhophiso Tataiso XTD2-0100F-J, XTH2, XTD2-0100F-J Temperature Transmitter, XTD2-0100F-J, Temperature Transmitter, Transmitter |
